Timer and Counter Instructions

Timers and counters control operations based on time or the number of events.

Available Instructions


If you want to:
Use this instruction:
time how long a timer is enabled
TON
time how long a timer is disabled
TOF
accumulate time
RTO
time how long a timer is enabled with built-in reset in function block
TONR
time how long a timer is disabled with built-in reset in function block
TOFR
accumulate time with built-in reset in function block
RTOR
count up
CTU
count down
CTD
count up and count down in function block
CTUD
reset a timer or counter
RES

The time base is 1 msec for all timers. For example, a 2 second timer’s .PRE value should be 2000.

Timer On Delay (TON)
The TON instruction is a non-retentive timer that accumulates time when the instruction is enabled (rung-condition-in is true).

Available Languages
-    Ladder Diagram


-    Function Block
This instruction is available in function block as TONR.
-     Structured Text
This instruction is available in structured text as TONR.

Operands

Operand
Type
Format
Description
Timer
TIMER
tag
timer structure
Preset
DINT
immediate
how long to delay (accumulate time)
Accum
DINT
immediate
total msec the timer has counted initial value is typically 0

TIMER Structure

Mnemonic
Data Type
Description
.EN
BOOL
The enable bit indicates the TON instruction is enabled.
.TT
BOOL
The timing bit indicates that a timing operation is in process.
.DN
BOOL
The done bit indicates that .ACC ³ .PRE.
.PRE
DINT
The preset value specifies the value (1 msec units) which the accumulated value must reach before the instruction sets the .DN bit.
.ACC
DINT
The accumulated value specifies the number of milliseconds that have elapsed since the TON instruction was enabled.


Example

Timer Off Delay (TOF)
The TOF instruction is a non-retentive timer that accumulates time when the instruction is enabled (rung-condition-in is false).

Available Languages
-     Ladder Diagram

-     Function Block
 This instruction is available in function block as TOFR.
-     Structured Text
 This instruction is available in structured text as TOFR.

Operands

Operand
Type
Format
Description
Timer
TIMER
tag
timer structure
Preset
DINT
immediate
how long to delay (accumulate time)
Accum
DINT
immediate
total msec the timer has counted initial value is typically 0

TIMER Structure

Mnemonic
Data Type
Description
.EN
BOOL
The enable bit indicates the TOF instruction is enabled.
.TT
BOOL
The timing bit indicates that a timing operation is in process.
.DN
BOOL
The done bit indicates that .ACC .PRE.
.PRE
DINT
The preset value specifies the value (1 msec units) which the accumulated value must reach before the instruction clears the .DN bit.
.ACC
DINT
The accumulated value specifies the number of milliseconds that have elapsed since the TOF instruction was enabled.

Example

When limit_switch_2 is cleared, light_2 is on for 180 msec (timer_2 is timing). When timer_2.acc reaches 180, light_2 goes off and light_3 goes on. Light_3 remains on until the TOF instruction is enabled. If limit_switch_2 is set while timer_2 is timing, light_2 goes off.


Retentive Timer On (RTO)
The RTO instruction is a retentive timer that accumulates time when the instruction is enabled.

Available Languages
-    Ladder Diagram

-    Function Block
This instruction is available in function block as RTOR.
-    Structured Text
This instruction is available in structured text as RTOR.

Operands

Operand
Type
Format
Description
Timer
TIMER
tag
timer structure
Preset
DINT
immediate
how long to delay (accumulate time)
Accum
DINT
immediate
total msec the timer has counted initial value is typically 0

TIMER Structure

Mnemonic
Data Type
Description
.EN
BOOL
The enable bit indicates the RTO instruction is enabled.
.TT
BOOL
The timing bit indicates that a timing operation is in process.
.DN
BOOL
The done bit indicates that .ACC .PRE.
.PRE
DINT
The preset value specifies the value (1 msec units) which the accumulated value must reach before the instruction clears the .DN bit.
.ACC
DINT
The accumulated value specifies the number of milliseconds that have elapsed since the RTO instruction was enabled.

Example

When limit_switch_1 is set, light_1 is on for 180 msec (timer_2 is timing). When timer_3.acc reaches 180, light_1 goes off and light_2 goes on. Light_2 remains until timer_3 is reset. If limit_switch_2 is cleared while timer_3 is timing, light_1 remains on. When limit_switch_2 is set, the RES instruction resets timer_3 (clears status bits and .ACC value).

Count Up (CTU)
The CTU instruction counts upward.

Available Languages
-    Ladder Diagram

-    Function Block
This instruction is available in function block as CTUD.
-    Structured Text
 This instruction is available in structured text as CTUD.

Operands

Operand
Type
Format
Description
Counter
COUNTER
tag
counter structure
Preset
DINT
immediate
how high to count
Accum
DINT
immediate
number of times the counter has counted initial value is typically 0

COUNTER Structure

Mnemonic
Data Type
Description
.CU
BOOL
The count up enable bit indicates the CTU instruction is enabled.
.DN
BOOL
The done bit indicates that .ACC  .PRE.
.OV
BOOL
The overflow bit indicates the counter exceeded the upper limit of 2,147,483,647. The counter then rolls over to -2,147,483,648 and begins counting up again.
.UN
BOOL
The underflow bit indicates that the counter exceeded the lower limit of -2,147,483,647. The counter then rolls over to 2,147,483,647 and begins counting down again.
.PRE
DINT
The preset value specifies the value which the accumulated value must reach before the instruction sets the .DN bit.
.ACC
DINT
The accumulated value specifies the number of transitions the instruction has counted.

Example

After limit_switch_1 goes from disabled to enabled 10 times, the .DN bit is set and light_1 turns on. If limit_switch_1 continues to go from disabled to enabled, counter_1 continues to increment its count and the .DN bit remains set. When limit_switch_2 is enabled, the RES instruction resets counter_1 (clears the status bits and the .ACC value) and light_1 turns off.


Count Down (CTD)
The CTD instruction counts downward.

Available Languages
-    Ladder Diagram

-    Function Block
 This instruction is available in function block as CTUD.
-    Structured Text
 This instruction is available in structured text as CTUD.

Operands

Operand
Type
Format
Description
Counter
COUNTER
tag
counter structure
Preset
DINT
immediate
how low to count
Accum
DINT
immediate
number of times the counter has counted initial value is typically 0

COUNTER Structure

Mnemonic
Data Type
Description
.CU
BOOL
The count down enable bit indicates the CTU instruction is enabled.
.DN
BOOL
The done bit indicates that .ACC  .PRE.
.OV
BOOL
The overflow bit indicates the counter exceeded the upper limit of 2,147,483,647. The counter then rolls over to -2,147,483,648 and begins counting up again.
.UN
BOOL
The underflow bit indicates that the counter exceeded the lower limit of -2,147,483,647. The counter then rolls over to 2,147,483,647 and begins counting down again.
.PRE
DINT
The preset value specifies the value which the accumulated value must reach before the instruction sets the .DN bit.
.ACC
DINT
The accumulated value specifies the number of transitions the instruction has counted.

Example

A conveyor brings parts into a buffer zone. Each time a part enters, limit_switch_1 is enabled and counter_1 increments by 1. Each time a part leaves, limit_switch_2 is enabled and counter_1 decrements by 1. If there are 100 parts in the buffer zone (counter_1.dn is set), conveyor_a turns on and stops the conveyor from bringing in any more parts until the buffer has room for more parts.


Reset (RES)
The RES instruction resets a TIMER, COUNTER, or CONTROL structure.

Available Languages
-    Ladder Diagram

-    Function Block
 This instruction is not available in function block.
-    Structured Text
 This instruction is not available in structured text.

Operands

Operand
Type
Format
Description
structure
TIMER
CONTROL
COUNTER
tag
structure to reset

Example
ExampleDescription
When enabled, reset timer_3.
When enabled, reset counter_1.
When enabled, reset control_1.


Timer On Delay with Reset (TONR)
The TONR instruction is a non-retentive timer that accumulates time when TimerEnable is set.

Available Languages
-    Ladder Diagram
 This instruction is available in ladder diagram as two separate instructions: TON and RES.
-    Function Block

-    Structured Text
 TONR(TONR_tag);

Operands

Operand
Type
Format
Description
TONR tag
FBD_TIMER
structure
TONR structure

FBD_TIMER Structure

Input Parameter
Data Type
Description
EnableIn

BOOL
Function Block:
If cleared, the instruction does not execute and outputs are not updated. If set, the instruction executes.
Default is set.
Structured Text:
No effect. The instruction executes.
TimerEnable
BOOL
If set, this enables the timer to run and accumulate time.
Default is cleared.
PRE
DINT
Timer preset value. This is the value in 1 msec units that ACC must reach before timing is finished. If invalid, the instruction sets the appropriate bit in Status and the timer does not execute.
Valid = 0 to maximum positive integer
Reset
BOOL
Request to reset the timer. When set, the timer resets.
Default is cleared.

 
Output Parameter
Data Type
Description
EnableOut
BOOL
The instruction produced a valid result.
ACC
DINT
Accumulated time in milliseconds.
EN
BOOL
Timer enabled output. Indicates the timer instruction is enabled.
TT
BOOL
Timer timing output. When set, a timing operation is in progress.
DN
BOOL
Timing done output. Indicates when accumulated time is greater than or equal to preset.
Status
DINT
Status of the function block.
InstructFault (Status.0)
BOOL
The instruction detected one of the following execution errors. This is not a minor or major controller error. Check the remaining status bits to determine what occurred.
PresetInv (Status.1)
BOOL
The preset value is invalid.

Example
Each scan that limit_switch1 is set, the TONR instruction increments the ACC value by elapsed time until the ACC value reaches the PRE value. When ACC ³ PRE, the DN parameter is set, and timer_state is set.

-    Function Block

-    Structured Text
TONR_01.Preset := 500;
TONR_O1.Reset := reset;
TONR_01.TimerEnable := limit_switch1;
TONR(TONR_01)
timer_state := TONR_01.DN;


Timer Off Delay with Reset (TOFR)
The TOFR instruction is a non-retentive timer that accumulates time when TimerEnable is cleared.

Available Languages
-    Ladder Diagram
 This instruction is available in ladder diagram as two separate instructions: TOF and RES.
-    Function Block

-    Structured Text
 TOFR(TOFR_tag)

Operands

Operand
Type
Format
Description
TOFR tag
FBD_TIMER
structure
TOFR structure

FBD_TIMER Structure

Input Parameter
Data Type
Description
EnableIn

BOOL
Function Block:
If cleared, the instruction does not execute and outputs are not updated. If set, the instruction executes.
Default is set.
Structured Text:
No effect. The instruction executes.
TimerEnable
BOOL
If set, this enables the timer to run and accumulate time.
Default is cleared.
PRE
DINT
Timer preset value. This is the value in 1 msec units that ACC must reach before timing is finished. If invalid, the instruction sets the appropriate bit in Status and the timer does not execute.
Valid = 0 to maximum positive integer
Reset
BOOL
Request to reset the timer. When set, the timer resets.
Default is cleared.

 
Output Parameter
Data Type
Description
EnableOut
BOOL
The instruction produced a valid result.
ACC
DINT
Accumulated time in milliseconds.
EN
BOOL
Timer enabled output. Indicates the timer instruction is enabled.
TT
BOOL
Timer timing output. When set, a timing operation is in progress.
DN
BOOL
Timing done output. Indicates when accumulated time is greater than or equal to preset.
Status
DINT
Status of the function block.
InstructFault (Status.0)
BOOL
The instruction detected one of the following execution errors. This is not a minor or major controller error. Check the remaining status bits to determine what occurred.
PresetInv (Status.1)
BOOL
The preset value is invalid.

Example
Each scan after limit_switch1 is cleared, the TOFR instruction increments the ACC value by elapsed time until the ACC value reaches the PRE value. When ACC ³ PRE, the DN parameter is cleared, and timer_state2 is set.

-    Function Block

-    Structured Text
TOFR_01.Preset := 500;
TOFR_01.Reset := reset;
TOFR_01.TimerEnable := limit_switch1;
TOFR(TOFR_01);
timer_state2 := TOFR_01.DN


Retentive Timer On with Reset (RTOR)
The RTOR instruction is a retentive timer that accumulates time when TimerEnable is set.

Available Languages
-    Ladder Diagram
 This instruction is available in ladder diagram as two separate instructions: RTO and RES.
-    Function Block

-    Structured Text
 RTOR(RTOR_tag)

Operands

Operand
Type
Format
Description
RTOR tag
FBD_TIMER
structure
RTOR structure

FBD_TIMER Structure

Input Parameter
Data Type
Description
EnableIn

BOOL
Function Block:
If cleared, the instruction does not execute and outputs are not updated. If set, the instruction executes.
Default is set.
Structured Text:
No effect. The instruction executes.
TimerEnable
BOOL
If set, this enables the timer to run and accumulate time.
Default is cleared.
PRE
DINT
Timer preset value. This is the value in 1 msec units that ACC must reach before timing is finished. If invalid, the instruction sets the appropriate bit in Status and the timer does not execute.
Valid = 0 to maximum positive integer
Reset
BOOL
Request to reset the timer. When set, the timer resets.
Default is cleared.

 
Output Parameter
Data Type
Description
EnableOut
BOOL
The instruction produced a valid result.
ACC
DINT
Accumulated time in milliseconds.
EN
BOOL
Timer enabled output. Indicates the timer instruction is enabled.
TT
BOOL
Timer timing output. When set, a timing operation is in progress.
DN
BOOL
Timing done output. Indicates when accumulated time is greater than or equal to preset.
Status
DINT
Status of the function block.
InstructFault (Status.0)
BOOL
The instruction detected one of the following execution errors. This is not a minor or major controller error. Check the remaining status bits to determine what occurred.
PresetInv (Status.1)
BOOL
The preset value is invalid.

Example
Each scan that limit_switch1 is set, the RTOR instruction increments the ACC value by elapsed time until the ACC value reaches the PRE value. When ACC ³ PRE, the DN parameter is set, and timer_state3 is set.

-    Function Block

-    Structured Text
RTOR_01.Preset :=500;
RTOR_01.Reset := reset;
RTOR_01.TimerEnable := limit_switch1;
RTOR(RTOR_01);
timer_state3 := RTOR_01.DN;


Count Up/Down (CTUD)
The CTUD instruction counts up by one when CUEnable transitions from clear to set. The instruction counts down by one when CDEnable transitions from clear to set.

Available Languages
-    Ladder Diagram
 This instruction is available in ladder as CTU, CTD, and RES.
-    Function Block

-    Structured Text
 CTUD(CTUD_tag)

Operands

Operand
Type
Format
Description
CTUD tag
FBD_COUNTER
structure
CTUD structure

FBD_COUNTER Structure

Input Parameter
Data Type
Description
EnableIn

BOOL
Function Block:
If cleared, the instruction does not execute and outputs are not updated. If set, the instruction executes.
Default is set.
Structured Text:
No effect. The instruction executes.
CUEnable
BOOL
Enable up count. When input toggles from clear to set, accumulator counts up by one.
Default is cleared
CDEnable
BOOL
Enable down count. When input toggles from clear to set, accumulator counts down by one.
Default is cleared
PRE
DINT
Counter preset value. This is the value the accumulated value must reach before DN is set.
Valid = any integer
Default is 0
Reset
BOOL
Request to reset the timer. When set, the counter resets.
Default is cleared

 
Output Parameter
Data Type
Description
EnableOut
BOOL
The instruction produced a valid result.
ACC
DINT
Accumulated value.
CU
BOOL
Count up enabled.
CD
BOOL
Count down enabled.
DN
BOOL
Counting done. Set when accumulated value is greater than or equal to preset.
OV
BOOL
Counter overflow. Indicates the counter exceeded the upper limit of 2,147,483,647. The counter then rolls over to -2,147,483,648 and begins counting down again.
UN
BOOL
Counter underflow. Indicates the counter exceeded the lower limit of -2,147,483,648. The counter then rolls over to 2,147,483,647 and begins counting down again.

Example
When limit_switch1 goes from cleared to set, CUEnable is set for one scan and the CTUD instruction increments the ACC value by 1. When ACC ³ PRE, the DN parameter is set, which enables the function block instruction following the CTUD instruction.

-    Function Block

-    Structured Text
CTUD_01.Preset := 500;
CTUD_01.Reset := Restart;
CTUD_01.CUEnable := limit_switch1;
CTUD(CTUD_01);
counter_state := CTUD_01.DN;